How to run a vent duct, chimney or riser through floors and take it out above the roof
WherePlan tabthe properties window of a vent ductchimney or riserShaft block
Steps
- Place the ventilation duct, chimney or riser on the lowest floor, where it starts.
- In the properties window, in the Shaft block, choose in the Runs field: Within this floor, To floor … or Above the roof. Above the roof is available for a vent duct, a chimney and a sewer riser.
- A chimney is placed right away as Above the roof.
What is important to know
- There is one shaft for all the floors it passes: it is visible on their plans with the same symbol and moves on any of them. A vent duct and a chimney are subtracted from the area of each floor, risers are not. On the floor above, furniture cannot be placed in the shaft.
- The outlet height follows SP 7.13130.2013, cl. 5.10, with Amendment No. 3 (in force from 01.07.2025), and depends on the distance to the nearest ridge:
- closer than 1.5 m: 0.5 m above the ridge;
- from 1.5 to 3 m: not lower than the ridge;
- farther than 3 m: not lower than a line going down from the ridge at 10°;
- above a flat roof: 2.0 m above it (before Amendment No. 3 it was 0.5 m).
- If there are several ridges (an L- or T-shaped house): the highest mark is taken. If there is no roof: the top-floor slab is treated as a flat roof.
- A sewer riser comes out above the roof as a soil vent pipe by 0.2 m, without a cap (SP 30.13330.2020, cl. 18.18). If an openable window or balcony is closer than 4 m horizontally, the riser window will warn you.